This paper presents a transient analysis of a unified power flow controller (UPFC), and design of capacitance of the DC-link capacitor. Active power flowing out of the series device in transient states is theoretically discussed to derive what amount of electric energy the DC link capacitor absorbs or releases through the series device. As a result, it is clarified that the active power flowing out of the series device is stored in the line inductance as magnetic energy during transient states. Design of capacitance of the DC-link capacitor is also presented in this paper, based on the theoretical analysis. Experimental results obtained from a 10-kVA laboratory setup are shown to verify the analytical results

Keywords
capacitance
control system analysis
load flow control
power capacitors
power system
control
transient analysis
Note
Digital Object Identifier: 10.1109/63.949506
Published with permission from the copyright holder. This is the institute's copy, as published in Power Electronics, IEEE Transactions on, Sep. 2001 , Volume 16, Issue 5, Pages 735-740.
Publisher URL:http://dx.doi.org/10.1109/63.949506
Copyright © 2001 IEEE. All rights reserved.
Published Date
2001-9
Publication Title
Power Electronics
Volume
volume16
Issue
issue5
Start Page
735
End Page
740
Content Type
Journal Article
language
English
Refereed
True
DOI
Submission Path
electrical_engineering/37